EPOCH-II
®
High-Current Output Unit
1000 VA of high current
Rugged, portable test set
Up to 187 Amperes maximum output
EPOCH-II
High-Current Output Unit
DESCRIPTION
The EPOCH-II
®
is a high-current output unit designed to
be controlled by the PULSAR
®
in combination with the
High-Current Interface Module to produce a rugged,
portable high-current, high-volt/ampere test set.
The EPOCH-II also is designed to be controlled by the
EPOCH-10
®
Relay Test Set.
PULSAR/EPOCH-II or EPOCH-10/EPOCH-II combination
uses microprocessor-based, digitally synthesized sine wave
generators and solid-state regulated power amplifiers to
provide sinusoidal voltage and current outputs with
precise control of the phase-angle relationships.
These combinations will produce accurate test results even
with a fluctuating power source or when testing nonlinear
or highly saturable relays.
An optional IEEE-488 GPIB interface transforms the
EPOCH-10/EPOCH-II combination into a programmable
automatic test system when used with an external
controller or computer. Amplitude and/or phase angle can
be set to desired values, step changed, ramped, or pulsed
to new values.
APPLICATIONS
PULSAR/EPOCH-II or EPOCH-10/EPOCH-II combination is
designed to test both complex protective relays which
require phase-shifting capability and simpler relays,
including all overcurrent relays.
The table above lists the different types of relays by
device numbers, and the different combinations of a
PULSAR or EPOCH-10s and an EPOCH-II required to test
them.
FEATURES AND BENEFITS
Output current source has a 5-minute duty cycle rating
of 1000 volt-amperes.
Four output ranges at 0.01 ampere and two output
ranges at 0.1 ampere are provided.
Tough steel, sealed enclosure provides a high shock
and vibration resistance.
Completely compatible with PULSAR via the High-
Current Interface Module and the EPOCH-10 units.
Device No. Relay Types Specify
One EPOCH-II and PULSAR
with High-Current Interface
Module or one EPOCH-10
One EPOCH-II and PULSAR
with Interface Module or two
EPOCH-10s
Instantaneous Overcurrent up
to 187 A at 1000 VA
Directional Overcurrent up to
187 A at 1000 VA
All of the above plus. . .
Differential
Distance
(open-delta)
50
67
87
21
One EPOCH-II and PULSAR
with Interface Modules or
three EPOCH-10s
Distance (wye)
21
Ground Directional
Overcurrent up to 187 A at
1000 VA
67N
Overcurrent up to 187 A at 1000 VA
51
Vue de la page 0
1 2 3

Résumé du contenu

Page 1 - High-Current Output Unit

EPOCH-II®High-Current Output Unit 1000 VA of high current Rugged, portable test set Up to 187 Amperes maximum outputEPOCH-IIHigh-Current Output UnitDE