Three-Phase TTR
®
Transformer Turns Ratio Test Set
Fully automatic operation
Measures three phases simultaneously
Highest ratio measurement (20,000:1);
highest accuracy (0.1%)
Built-in storage and downloading
capabilities
Measures ALL power transformers,
PTs and CTs
Displays % error vs. name plate and
pass/fail limits
Operator choice of “quick” test or
complete “full” test
Three-Phase TTR
®
Transformer Turns Ratio Test Set
DESCRIPTION
The Three-Phase Automatic TTR is designed to measure
the turns ratio of power, instrument, and distribution
transformers in a substation or manufacturing environment.
At 16.5 lbs (7.5 kg), it weighs less than any other
commercially available instrument. A rugged and robust
design makes this TTR well suited for use in a variety of
harsh environments. The TTR is also particularly suited for
testing in power transformer manufacturing environments
where testing of complex, three-phase substation power
transformers can be performed quickly while minimizing
the possibility of errors.
This new TTR measures the highest turns ratio range in the
industry (10,000:1) and also provides the highest accuracy
(0.1%). No other instrument’s performance is comparable
that is commercially available today.
Another excellent feature of this new TTR is the ability to
measure phase deviation (in minutes or centiradians) of
the transformer primary versus secondary. This will
quickly indicate problems in a transformer such as partial
shorted turns and core faults. This measurement is also
useful in verifying phase errors of all types of PTs and CTs.
The TTR also features special software capabilities. The
TTR comes equipped with sufficient onboard memory to
store up to 200 test results in the field for later retrieval in
the office. Test results can be printed on an optional serial
printer whenever a hard copy is desired, or the data can be
downloaded to a PC. Identification of individual test
readings is also easily done. The system software allows
entry of the transformer alphanumeric serial number,
transformer type and tap information for each test
performed.
This new TTR also comes with a unique optional, remote
control software program. This Windows
®
based program
permits control and operation from a PC keyboard,
download of test data from the TTR to a PC, print out a
test results report and assist in the preparation of management
and/or analysis reports using either Excel
®
or Access
®
.
Realizing the extreme environments in which the TTR must
operate, special attention has been paid to making it extra
rugged (with a hard, shock resistant case), yet incredibly
light weight (16.5 lbs). It features a high contrast LCD
screen which can be seen in bright or ambient light and
comes equipped with specially designed leads which
provide the necessary flexibility needed in cold weather
conditions.
APPLICATIONS
The proper operation of a transformer relies almost
entirely on the electrical properties of its windings. To
ensure continued proper operation, transformers are tested
to verify that their electrical properties have not changed
from design specifications.
A TTR is an extremely useful instrument for testing
transformer windings, because it can locate several types
of problems within a transformer. It is also ideal to use for
testing in Meter shops for the upcoming inspection of CTs
and PTs. It can determine the no load accuracy of all CTs
and PTs and also determine the need to further test faulty
CTs and PTs.
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - Three-Phase TTR

Three-Phase TTR®Transformer Turns Ratio Test Set Fully automatic operation Measures three phases simultaneously Highest ratio measurement (20,000:1);

Page 2

Three-Phase TTR®Transformer Turns Ratio Test SetThe new TTR applies voltage to the high voltage windingof a transformer and accurately measures the re

Page 3

Three-Phase TTR®Transformer Turns Ratio Test SetSPECIFICATIONSInput PowerCat. No. 550503:120 V ac ±10%, single phase, 50 ±2 Hz or 60 ±2 Hz, 100 VACat.

Page 4 - ORDERING INFORMATION

shift, excitation current, test date, test voltage, type oftransformer (single or three-phase), the configuration ofthe high and low voltage windings,